After countless forum discussions, phone calls from customers and lively debate, it is time to settle the earthing question once and for all. The question installers are faced with is whether a solar PV installation should be earthed.
Before we can delve into the key question, we need a basic understanding of some related topics and concepts.
Let us start by clarifying the different classes of electrical equipment. The paragraph below is copied from
the Swedish Electrical Safety Authority’s website:
Before we reach the main subject, some concepts need to be explained:
As solar cells are Class II electrical equipment, the solar PV installation must be isolated from earth. This insulation resistance must be monitored continuously using an IMD (insulation monitoring device). This means that if the insulation resistance is too low, the inverter must issue a warning. The inverter usually has this function built in; if it does not, the installation must be supplemented with this function. In practice, the inverter measures the resistance between the strings (positive and negative) and earth. For this measurement to be possible, there must be an earth reference to measure against, as earth is at zero potential.
Arc fault detection, or arc fault current interruption (AFCI), is a function that is becoming increasingly common and is built into inverters. This functionality is already available, for example, in Huawei and SolarEdge inverters sold in Europe, while SMA and Fronius only offer it in their US models. In short, arc fault detection uses a sensor that analyses the DC circuit. Smart algorithms identify any arcs, and the inverter then throttles production, extinguishing the arc.
Functional earthing on an installation with optimisers reduces EMC (electromagnetic compatibility) issues. Earthing the rail system (which is connected to the optimisers) dampens high-frequency signals. Put very simply, functional earthing can be seen as acting like a shock absorber that “dampens” certain interference issues.
From a purely installation-technical point of view, there is no difference between one earth and another. Functional earth may be taken from the protective earth terminal in the inverter. However, protective earth must not be taken from the functional earth cable. This is because that earthing does not protect against electric shock, for example by tripping a fuse. It must therefore not be called protective earth and must not be yellow-green.
If the property has a lightning protection system, or if there is a risk of induced interference, it is a good idea to consult a lightning protection professional about the design of such systems. Functional earthing, if carried out incorrectly, can contribute to an increased risk and render existing protection systems ineffective.
A separate earth electrode can be made using an iron rod or by burying a metal plate in the ground. The earth electrode is then connected to the roof by a DC cable. In practice, this means having a separate earth electrode for DC and AC.
The functional earth is connected to the same earth terminal as the other earths (both protective earth and functional earth).
Increased risk of induced voltage propagating into existing consumer units
The functional earth is connected to a separate earth terminal, but the terminal itself is connected to the same earth electrode. This is a compromise between options 1 and 2 listed above.
Having now read through this post, you will hopefully have gained even more knowledge and perhaps reached a greater consensus within the industry on the definitions and terms involved. As always with electrical installations, it is important to be familiar with the applicable standards and regulations. So make sure you have a good knowledge of these, while also checking what the inverter manufacturer actually requires for the installation.
We know it isn’t always easy to know which product or solution is best for you. Whether you have questions about our range, need guidance or want help finding a solution that suits your specific needs, we’re here for you. With our knowledge and experience, we’ll help you make the right choice.